Universal Generator Starter
Available at Solar Taos 2010 Product Catalog

Application

  • Used to control the starting and stopping of generators used as backup for battery based systems.
  • Generator starts if the battery voltage gets too low, and shuts off when the battery is near full.

Model: GS-1AC (without an NEMA-R3 enclosure)

TOP
Basic Operation

This Genset starter monitors the battery voltage, and when the battery voltage gets too its low setpoint, the unit starts the generator. When the battery gets to its high setpoint, the unit stops the generator. The generator may be remotely started and stopped by dry contact closures, or by its local toggle switch start stop commands. The setpoints may be temperature compensated with an optional remote temperature sensor.

Available in Model (GS-1AC) optimized for starting AC generators or Model (GS-1DC) for DC generators. This product is available in an enclosure or open frame design for mount in your own enclosure.

TOP
Features

  • Single unit 12 V up to 48 V battery systems
  • LEDs indicate relay positions and generator status
  • Temperature compensation (-4 mv / deg C./ cell) on start and stop voltages with optional temperature sensor TC-2
  • remote start and stop controls as well as local start/stop control
  • 5 second retirggerable time delay on voltage sensing to prevent false starts/stops
  • Supports 2, 3 and 4 wire systems as well as advanced control systems
  • Low Cost/ High Reliability

TOP
Electrical Specifications

  • Base Model: GS-1
  • Nominal battery voltages 12 - 48 V DC
  • Maximum Input (V) 63
  • Minimum Voltage 10
  • Relay: 8 amps @ 12/24 V , 2 amp @ 48 V , 5 amps @ 120 VAC rating of Potter and Brumfield T72 series relay
  • Self Consumption (A)
  • Relay Power: 0.5W per relay coil when powered, voltage independent
  • Quiescent less than 20 mA,Fusing 1 A, internal electronics only

TOP
Sequence of Operation on Startup

When the battery voltage is detected as too low per user adjustable setpoint the generator goes through its start sequence.

  1. The Generator start LED comes on.
  2. Precrank: 20 seconds relay closure (with LED on) prior to generator start/crank.
  3. Crank: relay closure (with LED on) for 10 seconds or until Genset start detected defined by generator/battery voltage starting to rise.
  4. Run: Relay closure (with LED on) whenever generator is cranking or running.
  5. Load: load relay closure (with LED on) for 30 seconds after run relay closure.
  6. If battery voltage falls another 0.2 V (relative to 12 V battery), fault relay is activated for remote signaling of fault.

TOP
Sequence of Operation on Shutdown

When the battery has charged to the user adjustable setpoint, the generator goes through its stop sequence.

  1. The Generator Stop LED comes on, start light turns off.
  2. Load: Load Relay opens (with LED off).
  3. Run: Run relay opens (with LED off) 20 seconds after load relay opens.
  4. Stop: Stop relay Closes (with LED on) for 10 seconds after run relay opens.

User Controls

  • Generator Stop Voltage
  • Generator Start Voltage
  • Manual start/stop toggle switch overrides remote smart stop control
  • Remote start/stop
  • Potentiometers and test points read 1/10 the voltage you wish to start/stop the generator. For example, if the generator is required to start at 23 V, set the start potentiometer for 2.3 V

TOP
LED Display

  • Generator start/stop
  • Relay position for precrank, crank, load, run, stop, fault

TOP
Mechanical Specifications

Weight:
  • GS-1 weighs 0.5 lbs. open frame
  • GS-2 weighs 8 lbs. NEMA 3R box
Size:
  • GS-1 measures 5" X 5" X 1" open frame
  • GS-2 measures 10" X 8" X 4" NEMA 3R box
Connections:
  • Power: Euro-style Terminal Strip # 12 AWG
Operating Temperature:
  • -40 to 60 deg. C
TOP
Humidity:
  • 0 - 90% non-condensing

Note: In the interest of continuous product improvement specifications subject to change without notice.

TOP
Models Available:

AC Model: Controls Gensets that have an AC generator powering a battery charger connected to the battery.
  • GS-1AC open frame for mount in user system
  • GS-2AC with NEMA 3R enclosure
DC Model: Controls Gensets that have a DC output directly to the battery.
  • GS-1DC open frame for mount in user system
  • GS-2DC with NEMA 3R enclosure

TOP


WE ACCEPT...

Sign up for PayPal and start accepting credit card payments instantly.

All transactions made on this site are secure and Hacker Safe. All Our Payments are processed through PayPal, a trusted company owned and operated by eBay.com
Prices are usually correct but subject to change, if there has been any change we will notify you . 
 

 If you are interested in quality supplements, please click on the above logo.
If you are interested in becoming a part of our USANA sales team, please click here.

Visit

Great gifts from Taos and northern
 New Mexico


American
Sign & Wood
Carving

Wood Care
Product

This page was designed and maintained by Terry R. Wolff